Teledyne 8800 Controller

  • Authorisation Mode allows locking of critical settings
  • Power supply options include both 150 and 600 watts
  • Ethernet with Modbus TCP serves/client & web server for configuration & monitoring

In StockMake An Enquiry

The 8800 controller combines the reliability of our proven 7800 controller with advanced upgrades in one low-cost package.

The 8800 controller provides simultaneous display and alarm functions for up to 16 input variables. 8 or 16 channel display modes and I/O modules arranged in groups of 8 channels allow economical system configuration. This easy-to-configure, user-friendly controller is ideal for centralising display and alarm functions in critical multipoint monitoring applications.

Features

  • 8/16 channel display modes accept inputs from many sensor types and signal ranges. Input types include 4-20mA and Modbus.
  • RS-485 serial ports allow simultaneous Modbus Master/Slave operation. Two standard ports and two optional isolated ports.
  • Three independent alarm levels per channel. “Relay Acknowledge” feature allows silencing of external audible devices during alarm conditions.
  • QVGA Colour LCD displays monitored data as trends, bar graphs and engineering units. Readouts change colours to indicate alarms.
  • Five standard SPDT 5-amp alarm relays. HORN, FAULT and three programmable alarm relays.
  • Options cards such as 4-20mA inputs, 4-20mA outputs, discrete and programmable alarm relays.
  • Cal Mode offers push-button zero/span calibration for remote sensor applications.
  • Data Logger onto SD card allows recording of input values and events for more than 10 years.
  • Magnetic keypad standard for non-intrusive operation in potentially hazardous locations.
  • Enclosures include wall mount NEMA 4X – Non-Metallic, 316 SS, XP, and Rack/Panel Mount.

    Enquire About This Product


    Title Size
    8800 Controller Datasheet 888 KB

    Additional information

    Weight 0.09 kg

    Specifications

    Input 12 bit 4-20mA into 150 ohms input impedance; includes +power supply terminals for each channel for routing power to two or three wire transmitters
    Serial Ports Two standard RS485 ports
      Two additional isolated ports optional
    Ethernet Port Modbus TCP Master/Slave port with web server (Gateway for Ethernet IP, Bacnet, and other protocols available)
    Alarm Relays 5 amp 30VDC or 250VAC resistive Form C
    Analog Outputs (Optional) 16 bit 4-20mA output. Max load 800 ohms with nominal 24VDC power supply
    Alarm Reset Two 10-60VDC Alarm Reset Input Terminals
    Digital Output 400mA @ VDC
    Display QVGA 320 x 240 pixel TFT graphic LCD with LED backlight
    Ambient Temperature Range -25 – +60 degrees C
    Power Supply 10 – 30VDC (24VDC nominal)
      12 Watts max required
      10-0172 option = 150 Watt
      10-0307 option = 600 Watt
    Approvals CE Approved
    CSA C22.2 No 1010.1 and C22.2
    No.152 for combustibles and ISA
    S82.02
    CSA Class I Div 2 Grps A, B, C, D