ABB Furse ESP 240CD40 Surge Protector

Code: 7TCA085460R0378
  • Full-mode design for continual operation of protected equipment
  • Repeated protection in lightning-intense environments
  • Earth connection. Screw terminal

In StockMake An Enquiry

The ESP 240CD40 is a combined Type 2 and 3 tested (to IEC/BS EN 61643) Surge Protective Device (SPD) for use on single-phase mains power distribution systems primarily to protect connected electronic equipment from transient overvoltages on the mains supply, e.g. computer, communications or control equipment.

For use at boundaries up to LPZ 1 through to LPZ 3 to protect sensitive electronic equipment.

Features & Benefits

  • Very low let-through voltage (enhanced protection to BS EN 62305) between all sets of conductors (phase to neutral, phase to earth, neutral to earth). Full Mode protection.
  • SPD includes a hybrid combination of MOVs and GDTs.
  • Innovative multiple thermal disconnect technology for safe disconnection from faulty or abnormal supplies (without compromising protective performance).
  • Three-way visual indication of protection status and advanced pre-failure warning, so you need never be unprotected.
  • Changeover active volt-free contact enables the SPD to warn of phase loss (i.e. power failure, blown fuses, etc).
  • Flashing warning of supply faults leading to increased neutral-to-earth voltage (supply faults due to incorrect earthing, wiring errors or unbalanced conditions) – prevents potentially unsafe installations.
  • Compact space-saving DIN housing with DIN release and locking feature for easy positioning onto DIN rail.
  • Large, robust terminals for straightforward connection of conductors.
  • Innovative design delivers zero leakage current to earth, so is suitable for TT and TN earthing systems.

Application

Install on single-phase supplies at final distribution board level to protect electronic equipment against transient overvoltages.

Installation

Install in parallel, within the power distribution board or directly (via fuses) onto the supply feeding equipment.

At distribution boards, the SPD can be installed either on the load side of the incoming isolator or on the closest outgoing way to the incoming supply.

Connect, with very short connecting leads, to phase, neutral and earth (see installation instructions).

Specifications

  • Nominal voltage – Phase-Neutral Uo (RMS) 240 V
  • Maximum voltage – Phase-Neutral Uc (RMS) 280 V
  • Temporary Overvoltage TOV UT(1) 350 V
  • Short circuit withstand capability 25 kA/50 Hz
  • Working voltage (RMS) 200-280 V
  • Frequency range 47-63 Hz
  • Max. backup fuse (see installation instructions) 125 A, parallel connection via series fuses to supply – see installation guide
  • Leakage current (to earth) Zero
  • Indicator circuit current < 10 mA (per phase, to neutral)
  • Volt free contact:(2) Screw terminal
  • Current rating 1 A
  • Nominal voltage (RMS) 250 V
  • Temperature range -40 to +80 °C
  • Connection type Screw terminal
  • Conductor size (stranded) 35 mm2 (solid), 25 mm2 (stranded) – maximum torque 4.5 Nm
  • Volt-free contact Connect via screw terminal with conductor up to 1.5 mm2 (stranded) – maximum torque 0.25 Nm
  • Degree of protection (IEC 60529) IP20
  • Case material FR Polymer UL-94 V-0
  • Weight: – Unit 0.25 kg
  • Dimensions to DIN 43880 – HxDxW(6) 90 mm x 88 mm x 36 mm (2TE)

Enquire About This Product

Title Size
ESP240CD40 Datasheet 765 KB

Additional information

Weight 0.09 kg