PRODUCT SPECIFICATIONS |
|
COMBUSTIBLE GAS SENSOR TYPE |
Catalytic Bead (Passive Comb, XCell Comb) |
|
Infrared (IR400) |
TOXIC GAS SENSOR TYPE |
Carbon Monoxide CO (XCell Toxic) |
|
Carbon Monoxide CO H2-Resistant (XCell Toxic) |
|
Hydrogen Sulfide H2S (Passive MOS, XCell Toxic) |
|
Oxygen O2 (XCell O2) |
|
Sulfur Dioxide SO2 (XCell SO2) |
SENSOR MEASURING RANGES |
Combustible: 0-100% LEL (CB, IR) |
|
CO: 0-100, 0-500, 0-1000 ppm |
|
CO H2-Resist: 0-100 ppm |
|
H2S MOS: 0-20, 0-50, 0-100 ppm |
|
H2S XCell: 0-10, 0-20, 0-50, 0-100 ppm |
|
O2: 0-25% |
|
SO2: 0-25 ppm |
TYPICAL SENSOR LIFE |
5 years – catalytic bead, MOS, XCell Sensor |
|
10 years – infrared |
APPROVALS CLASSIFICATION |
Divisions (US/Canada) |
|
Class I, Div 1&2, Groups A, B, C & D T5/T4; |
|
Class II, Div 1&2, Groups E, F & G, T6; Class III |
|
Type 4X, IP66 |
|
US Zones |
|
Class I, Zone 1 AEx db IIC T5 Gb |
|
Class I, Zone 2 AEx nA nC IIC T4 Gc |
|
Zone 21 AEx tb IIIC T85°C Db |
|
Canadian Zones/ATEX/IECEx |
|
Ex db IIC T5 Gb |
|
Ex nA nC IIC T4 Gc |
|
Ex tb IIIC T85°C Db |
|
(see manual for complete CSA listings) |
CE MARKING DIRECTIVES |
Complies with EMC, RED, ATEX |
WARRANTY |
S5000 transmitter: 2 years |
|
XCell Sensors: 3 years |
|
Passive Comb, Passive MOS, IR400: 2 years |
APPROVALS |
CSA, ATEX, IECEx,INMETRO, ABS, DNV-GL Marine, |
|
CE Marking. Complies with C22.2 No. 152, FM |
|
6320, ANSI/ISA/CSA/IEC/EN 60079-29-1, |
|
ANSI/ISA 12.13.01. Suitable for SIL 2. |
DIMENSIONS |
|
HOUSING (W X H) |
6.37’’ x 5.38’’ [162 mm x 137 mm] |
W/ PASSIVE SENSOR |
6.37’’ x 7.62’’ [162 mm x 193 mm] |
W/ DIGITAL SENSOR |
6.37’’ x 10.4’’ [162 mm x 265 mm] |
LID (DEPTH) |
4.25’’ [108 mm] |
WEIGHT |
8.0 lbs (3.6kg) – 316 SS |
ENVIRONMENTAL SPECIFICATIONS |
|
OPERATING TEMPERATURE RANGE |
Transmitter: -55°C to + 75°C |
|
CB (sintered, Zones): -40°C to +70°C |
|
CB (screened, Div): -40°C to +75°C |
|
MOS (sintered, Zones): -40°C to +70°C |
|
MOS (screened, Div): -40°C to +75°C |
|
IR (CSA): -40°C to +75°C |
|
IR (ATEX/IECEx): -60°C to +75°C |
|
XCell (Comb): -55°C to +60°C |
|
XCell (Toxic/O2): -40°C to +60°C |
STORAGE TEMPERATURE RANGE |
-50°C to +85°C (housing, IR400 and passive sensors) |
|
-40°C to +60°C (XCell sensors) |
OPERATING HUMIDITY RANGE |
10 to 95% (XCell sensors, IR400) |
|
10 to 90% (Passive Comb) |
|
0 to 95% (Passive H2S) |
MECHANICAL SPECIFICATIONS |
|
INPUT POWER |
24 VDC nominal, 12 to 30 VDC |
|
|
SIGNAL OUTPUT |
Dual 4-20 mA current source, HART, Modbus, |
|
Bluetooth. Optional: w/o Bluetooth |
RELAY RATINGS |
5A @ 30VDC; 5A @220 VAC |
|
(3X) SPDT – fault, warn, alarm |
RELAY MODES |
Common, discrete, horn |
NOMINAL MAX POWER (W/ RELAYS) |
Passive Comb 6.0 W |
|
Passive MOS 10.8 W |
|
IR400 8.9 W |
|
XCell Comb 6.0 W |
|
XCell Toxic & O2 3.6 W |
|
IR400 + XCell Comb 11.8 W |
|
IR400 + XCell Toxic or O2 9.6 W |
|
Dual XCell Toxic or O2 4.3 W |
|
Dual XCell Comb 8.4 W |
|
XCell Comb + XCell Toxic or O2 6.7 W |
STATUS INDICATORS |
4-digit scrolling LED, icons depicting fault, warn, alarm, Bluetooth, 1 and 2 to indicate sensor reading displayed |
RS-485 OUTPUT |
Modbus RTU, suitable for linking up to 128 units or up to 247 units with repeaters |
BAUD RATE |
2400, 4800, 9600, 19200, 38400, 115200 |
HART |
HART 7, HART device description language available |
FAULTS MONITORED |
Low supply voltage, RAM checksum error, flash checksum error, EEPROM error, internal circuit error, relay, invalid sensor configuration, sensor faults, calibration faults, analog output mismatch fault |
CABLE REQUIREMENTS |
3-wire shielded cable for single sensor and 4-wire shielded cable for dual sensor configurations. Accommodates up to 12 AWG |
|
Refer to manual for mounting distances. |