MSA remote sensors, Series 47K, are designed to detect potentially hazardous air concentrations of flammable gas and vapour.

A cost-effective range of sensors for detecting up to 100 % LEL, including Poison Resistant and High Temperature versions.

Series 47K sensors are available with either Ex d – 3/4″ NPT or Ex e–M25 junction boxes.

A complete range of accessories for calibration, environmental protection, sampling and duct mounting makes it suitable for virall combustible gas detection applicationseries 47K sensors used in combination with MSA Controllers fully meet the requirements of ATEX Directive 2014/34/EU, including performance, and being SIL 2 capable they can be used as part of a safety related system.

Features 

  • 0–100% LEL.
  • Ex e junction box with M25 cable gland thread.
  • Ex d junction box with 3/4″ NPT cable gland thread.
  • Poison Resistant (PRP) and High Temperature (HT) versions.
  • Suitable for safety-related systems (ATEX 2014/34/EU).
  • 3 or 5 wire connection.
  • Stainless steel body.
  • Complete range of accessories.
  • Fast response time.
  • Excellent performance cost ratio.
  • Safety Integrity Level – SIL 2.

Order Information

M25 Gas Detector (Sensor & Junction Box; stainless steel 316)
10114106 S47K-PRP, Det., M25, MSA hous., screw
10114109 S47K-PRP, Det., M25, MSA hous., spring
10123076* S47K-PRP, Detector, M25, screw, cal.
10123095* S47K-PRP, Detector, M25, spring, cal.
NPT Gas Detector (Sensor & Junction Box; stainless steel 316)3
10114107 S47K-PRP, Det.,3/4″NPT, MSA Hous., screw
10114110 S47K-PRP, Det.,3/4″NPT,MSA Hous., spring
10178833* Detector S47K-PRP, NPT, spring, cal.
10178834* Detector S47K-PRP, NPT, screw, cal.
Notes: *To be ordered together with a customised controller
M25 Sensor
10048118 S47K-PRP, Sensor, St.St.316, M25x1,5
10147537 S47K-HT-PRP, Sensor, V4A, M25x1,5, 2m
10185325 Detector S47K-HT PRP, M25, 10m cable
10147541* S47K-HT-PRP, Sens, V4A, M25, 2m, kal.
10185386* Detector S47K-HT PRP, M25, 10m cab, cal
Notes: *To be ordered together with a customised controller
NPT Sensor
10048272 S47K-PRP, Sensor, St. St. 316, 3/4 “NPT
10147542 S47K-HT PRP, Sensor, V4A, 3/4″NPT, 2m
Junction Box & Wall Mount Bracket
10114111 Series 47K MSA Housing EExe, screw
10114112 Series 47K MSA Housing, EExd, screws
10114114 Series 47K MSA Housing EExe, spring
10114115 Series 47K MSA Housing, EExd, spring
10048829 Wall mounted bracket, Sensor S47K HT
10151980 HT junction box 100 °C
Accessories
10112789 Calibration cap
10051623 S47K WEATHER PROTECTION, HOSE,316
10051731 S47K Weather p.cap NPT-Pipe connector 316
10113031 Flow adapter PrimaX & S47K
10105760 S47K, adapter f. MSA enclosure
10053551 Mounting sheet e-junction.box 90×90 S47k
10054042 S47K Mounting S. E-junct.b.+accessories
10150921 PrimaX Remote calibration splash guard (CalGard)
10045912 S47K, Manual, CD
10045913 S47K, Instruction card
10145118 S47K, SPARES KIT F. WEATHER PROTECTION
10204039 Gasket set S47K

Enquire About This Product

Title Size
Series 47K Datasheet 2 MB

Additional information

Weight 0.190 kg

Specifications

Power consumption 1 watt typical
Measuring range 0-100 % LEL
Response time T50 ≤10 sec. T90 ≤30 sec.
Operating life 3 years minimum in clean air @ STP
Storage life 5 years minimum in MSA container @ STP
Storage temperature -20 °C to +40 °C
Operating temperature range -40 °C to +55 °C (PRP)
-40 °C to +90 °C (extended range*)
-40 °C to +160 °C (HT)
Operating humidity range 5 % to 95 % RH non-condensing
Operating pressure range 100 ±20 kPa
Air velocity 0 – 6 m/s (with duct mount flange 0.5 – 20 m/s)
Poison resistance PRP sensor only: 10 ppm HMDS for 40 min. (max. signal loss 5% of reading)
Weight ca. 230 g (St.St. sensor)
Dimension Ø 36 x 56 mm
Material Stainless steel
Accessory thread M36 x 1.5 mm
Sensor to junction box 3/4” NPT or M25 x 1.5 mm
Approvals EU Type Certificate:
II 2GD INERIS 03 ATEX 0208
Safety Integrity Level SIL 2 (IEC 61508)
*Extended range: The sensor extended temperature range is greater than the maximum specified in EN 61779-1-4. It is therefore strongly recommended that if used above +55 °C the sensor is calibrated at the
operating temperature.