Linesense DLI-10K Digital Location Interface

Code: 52100-002 & 52100-004
  • IEC61508 certified & SIL2
  • Monitoring distance 10km
  • LED fire & fault indicators

In StockMake An Enquiry

The Linesense DLI-10K Digital Location Interface (DLI) monitors the Linear Heat Detection (LHD) cable and, when activated, identifies the alarm’s location—providing detection and location along the complete length of the LHD cable. The distance in meters is then displayed on the four-digit LCD.

With the ability to monitor up to 10,000m for both Fire and Fault conditions, the DLI enhances any fire detection capability and allows appropriate action to be taken.

The DLI offers flexible interfacing options, designed as a two-wire device for connecting directly to a conventional fire alarm panel; it also can signal via volt free relay contacts for Fire and Fault, plus a 4-20 mA output representing 0 to 10,000 metres.

Features

  • Detection & display of Alarm location for the complete length of LHD cable, from 0- 9,999m
  • Four-digit LCD
  • Fire and fault test functions
  • DIN rail mounted or IP 65 Housing available
  • Volt free relay outputs for Fire and Fault
  • 4-20mA output
  • Configurable for two-wire mode
  • Remote reset input

Order Information

The DLI is available as a DIN Rail mountable unit or fitted into an IP 65 weatherproof enclosure.

52100-002 Digital Location Interface DLI-10K with LCD distance location indicator to Fire signal 10,000m max. Fire and Fault relay outputs, LED Indicators, test switches, and 4-20mA, IP65 Polycarbonate enclosure.

52100-004 Digital Location Interface DLI-10K with LCD Distance Location indicator to Fire signal 10,000m max. Fire and Fault relay outputs, LED Indicators, test switches, and 4-20mA, DIN Rail mounted.

Enquire About This Product

Additional information

Weight 0.09 kg

Specification

ELECTRICAL

Operating voltage: 14 – 30 VDC Two-wire mode. 20 – 30 VDC Relay mode
Operating Current Normal: 1.7 mA Two-wire mode. 11.5 mA Relay mode
Fire Alarm (max): 12 mA Two-wire mode. 29 mA Relay mode
Fault Condition: 700 uA

Output

Fire: 2 x VFCO relays, 1 amp 24 VDC / 120 VAC Resistive
Fault: 2 x VFCO relays, 1 amp 24 VDC / 120 VAC Resistive
4 – 20 mA signal loop output
LCD: 4 Digit (Accuracy ±1 digit, Tolerance ±3%)
Inputs: Remote Reset
The maximum length of LHD: is 10,000m

MECHANICAL

Dimensions: H105 x W86 x D58 mm (DIN Rail version). H200 x W164 x D116 mm (Polystyrene enclosure).
Cable entries : 4 x M20, 1 x M25 Top. 4 x M20, 1 x M25 Bottom. 2 x M20 each side.

Enquire About This Product