Honeywell’s FSL100 range of Light Industrial/Commercial Flame Detectors enables simple coverage of fire hazard areas across many fire hazard applications. Installation, set-up and operation are simple. Wide solid area coverage and fast speed of response optimise safety. Reliability is ensured with inbuilt automatic test and test lamps available to cover all models.
The newest Optoelectronic flame detector for a wide range of Light Industrial fire detection from Honeywell Analytics. With three versions to cover a wide range of flaming fires: Ultraviolet (UV), Ultraviolet/Infrared (UV/IR) and Triple Infrared (IR3). Addresses a wide range of fire protection applications both indoors and outdoors.
Detects a wide range of Hydrocarbon & Non-Hydrocarbon fires means that many application areas can be addressed. Optical detection of radiant energy in a solid angle field of view enables coverage of a large risk area. A simple optional mounting bracket allows the FSL100 to be installed and aligned, covering the hazard. The fast response is far quicker than other technologies by responding to flaming fires in seconds, enabling a more rapid response to danger before the fire can escalate.
Can be installed indoors or outdoors and in Hazardous areas, typically looking into a Div 1 area from a distance. Relay and current output (Fault and Alarm) Analogue stepped output and Alarm/Fault relays for simple connectivity. Inbuilt Automatic Test and Simple to use Test Lamps FSL100 maintains continuous internal health monitoring. Test lamps enable simple operational and Field of View testing.
Features
- UV, UV/IR and IR3 Flame Detectors to cover a wide range of applications
- Robust, simple to install & set up: Wide angle and fast speed of response
- Automatic test and test lamps for simple check and maintenance
Specification
- FSL100 Flame Detectors – UV, UV/IR and IR3 for light industrial applications
- FM Class 1, 2 & 3 Div 2
- FM 3260 performance certified
- GRP Housing, available in Red or White with an optional swivel mount
- 12-14Vdc, 25mA nominal operation
- 4 to 20mA and Relay outputs
- Dimensions 4.9 x 3.15 x 2.25 inches (125 x 80 x 57 mm). Weight 1.05 lb (465 g)
Order Information
Note: A swivel mount should be ordered with each flame detector.
UV (Ultraviolet) Flame Detector
FSL100-UV UV flame detector. For ATEX zone 2/22; FM 3611 Class 1,2&3 Div2EN54-10 (HIGH sensitivity) certificate. FM3260 approval. Red Housing
FSL100-UV-W UV flame detector. For ATEX zone 2/22; FM 3611 Class 1,2&3 Div2EN54-10 (HIGH sensitivity) certificate FM3260 approval. White Housing
UVIR (Ultraviolet & Infrared) Flame Detector
FSL100-UVIR UV/IR flame detector. For ATEX zone 2/22; FM 3611 Class 1,2&3 Div2EN54-10 (HIGH sensitivity) certificate. FM3260 approval. Red Housing
FSL100-UVIR-W UV/IR flame detector. For ATEX zone 2/22; FM 3611 Class 1,2&3 Div2EN54-10 (HIGH sensitivity) certificate FM3260 approval. White Housing
IR3 (3 Infrared bands) Flame Detector
FSL100-IR3 Triple IR flame detector. For ATEX zone 2/22; FM 3611 Class 1,2&3 Div2EN54-10 (HIGH sensitivity) certificate. FM3260 approval. Red Housing
FSL100-IR3-W Triple IR flame detector. ATEX zone 2/22; FM 3611 Class 1,2&3 Div2EN54-10 (HIGH sensitivity) certificate. FM3260 approval. White Housing
Accessories
FSL100-SM21 FSL100 Optional swivel mount
FSL100-TL FSL100 test lamp, incl. universal charger and carrying case; non-EX
FSL100-TLX FSL100 test lamp, incl. carrying case; intrinsically safe
Spare Parts
FSL100-TLBT 12 Vdc battery for FSL-TL test lamp
FSL100-TLBU H3 light bulb for FSL-TL test lamp
FSL100–TLCH Universal charger kit for FSL-TL test lamp