General Monitors IR5500 Open Path Infrared Gas Detector

Code: IR5500-1-1-1-1-2-2-1-1-2-1
  • Continuous monitoring for flammable gas leaks
  • For large open areas
  • Monitors LEL-m & ppm-m ranges

In StockMake An Enquiry

The General Monitors IR5500 is an open-path IR gas detector that continuously monitors hydrocarbon gas concentrations. The system consists of an IR source and receiver that continuously monitor light hydrocarbons in the 0 to 5000 ppm and 0 to 5 LEL meter ranges.

A meter with a 0 to 2000 ppm range and a 0 to 1 LEL range is also available for monitoring heavy hydrocarbons. The IR5500 provides two 4-20 mA analogue signals proportional to the above ranges, a digital display, and relay contacts.

The IR5500 is easily aligned using the digital display and adjustable mounting arms. Therefore, it does not require bulky setup equipment (e.g., digital voltmeters, handheld alignment aids).

The IR5500’s sensitivity can be checked by placing a test gas film in front of the receiver.

The IR5500 is factory-calibrated and does not require any additional calibration. It also requires minimal maintenance, aside from periodic visual inspections, a test gas film check, and window cleaning, to ensure dependable performance.

Sensor data and status information from the IR5500 can be transmitted up to 9,000 feet (2,743 m) to any industrial analogue-to-digital (A/D) converter for multipoint computer-based monitoring.

IR5500 receiver part number 329000. IR5500 transmitter (source) part number 329001.

Features

  • Dual detection ranges are sensitive to both small (ppm•meter) and large (LEL•meter) gas leaks.
  • Performance approved for use in harsh environments.
  • Single detection beam improves accuracy and reduces drift.
  • Continuous self-check provides a fail-safe operation.
  • Multiple communication outputs provide complete status and control capability in the control room.
  • Unitised display allows ease of operation.
  • Automatic gain control compensates for dirty optics, rain, and fog.

    Enquire About This Product


    Title Size
    IR5500 Datasheet 103 KB
    IR5500 Configurator 46 KB

    Additional information

    Weight 0.190 kg

    Specifications

    System Specifications
    SENSOR TYPE Infrared Absorption
    DUAL RANGES
    METHANE 0 to 5000 ppm• meter
    0 to 5 LEL• meter
    PROPANE 0 to 2000 ppm• meter
    0 to 1 LEL• meter
    Consult factory for other hydrocarbon gases available
    PATH LENGTHS 5-30 m, 20-100 m, 80-150 m
    RESPONSE TIME T90 ≤ 3 s
    REPEATABILITY ≤ ±5%
    LINEARITY ≤ ±5% of full scale for each scale
    or ±10% of applied gas, whichever is greater
    CLASSIFICATION CSA/FM:
    Class I, Div 1 & 2, Groups B, C, & D;
    Class II, Div 1 & 2, Groups E, F, & G
    Class III; Type 4X
    HAZ LOC T3C (Tamb=-60°C to +75°C)
    PERFORMANCE T4 (Tamb=-50°C to +65°C)
    VERIFIED ATEX/IECEx:
    II 2 G D, Ex d IIB+H2 T4 Gb Ex tb IIIC
    T135°C Db, IP66/67
    (Tamb=-55°C to +65°C)
    CALIBRATION No calibration required.
    Field background zero adjustment provided
    MODES Setup, alignment, test mode
    ACCESSORIES Test gas films, mounting arm, mounting base, scope, attenuation plate
    WARRANTY Two years
    APPROVALS CSA, FM, ATEX, IECEx, DNV-GL, INMETRO, EAC, CE. SIL 3 suitable. HART registered.
    Mechanical Specifications
    HOUSING 316 stainless steel
    SOURCE 5.3″ dia. x 12.4″ length
    (135 mm dia. x 315 mm length)
    RECEIVER 5.3″ dia. x 12.4″ length
    (135 mm dia. x 315 mm length)
    WEIGHT Source: 12.20 lb. (5.53 kg)
    Receiver: 12.34 lb. (5.60 kg)
    CONDUIT ENTRIES (2) ¾” NPT (standard), M25 (optional)
    Environmental Specifications
    OPERATING TEMPERATURE RANGE -67°F to +149°F (-55°C to +65°C)
    OPERATING HUMIDITY RANGE 10-95% RH, non-condensing
    Electrical Specifications
    INPUT POWER 20 to 36 VDC range, 24 VDC nominal
    24 VDC @ 12 W (max.) – source
    24 VDC @ 10 W (max.) – receiver (w/relays)
    Consult factory for lower power consumption options for other configurations
    RELAY RATINGS 8 A @ 250 VAC/8 A @ 30 VDC res. max.
    Four (4) SPDT – Fault; ppm Warning, LEL Warning; and Alarm
    RS-485 OUTPUT Modbus RTU with block and single data transfer modes
    BAUD RATE 2400, 4800, 9600, 19200, or 38400 BPS
    HART Fully HART compliant
    EMC PROTECTION Complies with EN 61000-6-4 and EN 50270
    SAMPLE CABLE DISTANCES For cable resistance of 3 ohms/1,000 ft., maximum distance between IR5500 and power source @ 24 VDC:
    14 AWG – 1,330 ft. (405 m) – receiver,
    14 AWG – 1,040 ft. (317 m) – source.
    DIGITAL DISPLAY LED indication of scale displayed; Two digit, seven segment (auto range change)
    STANDARD CONFIGURATION IR5500-1-1-1-1-2-2-1-1-2-1
    Methane, Dual 0-20 mA, HART, relays, mounting arm, 20-100 m path length
    * HART units can be configured to never output current less than 3.5 mA if the host equipment is incapable of working below this level.
    ** 0 to 2000 ppm• meter and 0 to 1 LEL• meter on propane unit.
    *** Using optional split range.