Crowcon Sensitron Multiscan++PK

  • EN-Approved Control Panel for Car Parks
  • Up to 16 inputs (both 4-20 mA and loop daisy-chained)
  • 1 open RS485 (EIA-485)

In StockMake An Enquiry

The Multiscan++PK gas detection control panel supports a maximum of 256 detectors and has been designed with car parks in mind. It complies with the EN 50545-1 standard, which defines the requirements for detecting CO and NO2 in car parks and tunnels.

Self-testing

The system’s powerful microprocessor allows a wide range of self-testing facilities to detect and localise possible failures.

Designed for car parks

Multiscan++PK has been designed with car parks in mind and complies with the EN 50545-1 standard, which defines the requirements for detecting CO and NO2 in car parks and tunnels.

Up to 256 detectors

Multiscan++PK supports a maximum of 256 detectors with both RS485 communication loop connected and 4-20 mA via STG/IN8-PK modules.

Order Information

MULTISCAN++ PK
CRMTS/PK-256B MULTISCAN++PK gas control panel. 4 x RS485 open bus lines or two closed loops. 256 Analog 4-20 mA gas detectors connected through remote 8-input modules or addressable gas detectors daisy chained to the RS485 control panel’s loops and 8 x 4-20 mA inputs on-board the panel.8 relay outputs and up to 512 O/C or relay outputs via remote modules. The panel comes complete with 1 parallel printer port and 1 RS232 serial port for PC connection. Housed in IP65 rated ABS box
CRMTS/PK-256 Rack version of STMTS/PK-256B. The panel comes housed in a 19” 6 U rack (24 Vdc power supply is required).
CRMTS/PK-128B MULTISCAN++PK gas control panel. 4 x RS485 type open bus lines or two closed loops. 128 Analog 4-20 mA gas detectors connected through remote 8-input modules or addressable gas detectors daisy chained to the RS485 control panel’s loops and 8 x 4-20 mA inputs on-board the panel. 8 relay outputs and up to 256 O/C or relay outputs via remote modules. The panel comes complete with 1 parallel printer port and 1 RS232 serial port for PC connection. Housed in IP65 rated ABS box
CRMTS/PK-128 Rack version of STMTS/PK-128B. The panel comes housed in a 19” 6 U rack (24 Vdc power supply is required).
CRMTS/PK-64B MULTISCAN++PK gas control panel. 2 x RS485 type open bus lines or one closed loop. 64 Analog 4-20 mA gas detectors connected through remote 8-input modules or addressable gas detectors daisy chained to the RS485 control panel’s loops and 8 x 4-20 mA inputs on-board the panel. 8 relay outputs and up to 256 O/C or relay outputs via remote modules. The panel comes complete with 1 parallel printer port and 1 RS232 serial port for PC connection. Housed in IP65 rated ABS box
CRMTS/PK-64 Rack version of STMTS/PK-64B. The panel comes housed in a 19” 6 U rack (24 Vdc power supply is required).
CRMTS/PK-32B MULTISCAN++PK gas control panel. 2 x RS485 type open bus lines or one closed loop. 32 Analog 4-20 mA gas detectors connected through remote 8-input modules or addressable gas detectors daisy chained to the RS485 control panel’s loops and 8 x 4-20 mA inputs on-board the panel. 8 relay outputs and up to 256 O/C or relay outputs via remote modules. The panel comes complete with 1 parallel printer port and 1 RS232 serial port for PC connection. Housed in IP65 rated ABS box
CRMTS/PK-32 Rack version of STMTS/PK-32B
CRMTS/PK-8D MULTISCAN++PK gas control panel. 1 x RS485 type open bus line. 8 addressable gas detectors daisy chained to the RS485 control panel’s loops and 4 x 4-20 mA inputs on-board the panel. 5 relay outputs and additional 16 via remote STG/OUT16S card. The panel comes complete with 1 USB port for PC connection. Housed in plastic box for din-rail mounting
MULTISCAN++ PK ACCESSORIES
STG/IN4-OUT4-PK Remote module with 4 inputs 4-20mA and 4 output relays for MULTISCAN++PK
STG/IN8-PK 8 input remote module for MULTISCAN++ Park control panel.
STG/OUT16S High safety 16-output remote module (Open collector type) with improved performance. Max 8 modules per line, for a total of 16 modules connectable to the system. For STMTS/PK-64B and STMTS/PK-32B max 8 modules connectable to the system
STG/8REL Plug and play relay board to be connected to STG/OUT16 to provide 8 relay outputs
STG/SER++ Additional Serial board for MULTISCAN++PK-64 & 64B
STG/TCPIP-C TCP/IP interface for LAN connection
AL11/276V5 Power supply 27.6 Vdc 5A in Metal cabinet
STG/BOX IP55 Plastic box to house one STG/IN8-PK or STG/OUT16S card
STG/32-85 RS232/RS485 Interface for PC connection on RS485 line of MULTISCAN++
STMTS/RTU Din rail mounted remote unit for events visualization. To be RS485 connected to MULTISCAN++S1, PK & MULTISCAN 8+ serial lines, it allows the visualization and identification of events. RTU comes complete with an LCD display to show different information as alarm or fault, 4 analogue 4-20 mA inputs for detectors connection and 5 output relays freely programmable.
AL09 24 Vdc power supply for STPL4+D & STMTS/RTU
STG/IPBOX IP65 ABS box for STPL4+D & STMTS/RTU

Enquire About This Product

Title Size
Multiscan++PK Datasheet 8 MB

Additional information

Weight 0.190 kg

Specifications

Size H470 x W426 x D148 mm (18.5 x 16.77 x 5.83ins)
Weight Rack version: 4.5 kg
Box version: 6.6 kg (without batteries)
Enclosure material ABS or aluminium rack
Power Box version: power supply with Vout=27.6 Vdc / Iout=4A, Vin=110 Vac or 220 Vac selectable by a manual switch. Possibility to place two 12V 7Ah batteries.
Rack version: connect to an external 24Vdc power supply
Operating temperature 0 / +50°C
Humidity 15 / 85% RH non condensing
Inputs 8 inputs 4-20 mA on board, additional inputs available via the remote modules. Sensitron gas detectors can be also connected directly on RS485 bus. The total inputs number depends on the gas panel model:
Multiscan++ 256: up to 256 inputs
Multiscan++ 128: up to 128 inputs
Multiscan++ 64: up to 64 inputs
Multiscan++ 32: up to 32 inputs
Multiscan++ 16: up to 16 inputs
Outputs Multiscan++ 256/128/64/32: 8 relays on board Mutliscan++ 16: 6 relays on board
Additional outputs available via the remote modules, the total outputs number depends on the gas panel model: Multiscan++ 256: up to 516 outputs
Multiscan++ 128: up to 256 outputs
Multiscan++ 64: up to 128 outputs
Multiscan++ 32: up to 64 outputs
Multiscan++ 16: up to 32 outputs
Communication Port Galileo or Modbus for field communication
Modbus for the supervision
Event logging The event log can be visualised from the gas panel or by the software
Panel indication LCD display
18 status LEDs
Approvals EMC
Functional Safety SIL2