Crowcon GM Addressable Controllers

  • Multiple channel capacity options (16 / 64 / 128)
  • Customisable controller configuration
  • Addressable capability

In StockMake An Enquiry

Crowcon’s range of addressable gas detection controllers are easy to configure and are very user-friendly.

There are 3 controller options with different channel input variables.

Local non-intrusive operation & display with simultaneous live reading display and alarm functions via colour LCD display.

There is also a ‘direct to web page’ live feed communication feature for viewing or taking action remotely.

There are 3 addressable gas detection controller options with identical functionality but different channel input capabilities.

  • GM16: 1-16 Channel inputs
  • GM64: 1-64 Channel inputs
  • GM128: 1-128 Channel inputs

All are available as 19” rack mounted, with enclosure options available for GM16 & GM64.

Our addressable gas detection controllers are modular and can be configured according to requirements. To reduce complexity and cost, only include what is needed for the application.

Capability:

  • LCD display provides simultaneous visibility for all live channel readings and alarm functions in system setup (up to 64 input variables)
  • 4-20ma analogue & RS-485 Modbus communications are standard, and HART-compatible communications are enabled.
  • Direct to web page live feed communication for remote viewing and acknowledgement actions
  • Flexible configuration options allow the ability to name controller, name zones, set the alarm & relay setpoints
  • Ability to group channels into zoned areas

Functions:

  • Main data screen – Displays all active channels on the same screen. Cells indicate alarm status by colour
  • Bar graph screen – Display 16 channels at a time, side scroll bar for clear coloured indicator for focused channel alarm status
  • 24-hour trend screen – Review 24-hour gas monitor trend for a single channel at a time
  • 3-minute trend screen – Review the most recent 30-minute trend for a single channel at a time
  • Zone screen – Display up to 8 active zones on a single screen. Individual channels within zone visibility

Order Information

Controller type
GM RANGE OF ADDRESSABLE CONTROLLERS
Channel capability / Power supply / Mounting
016ZS GM16 – 16 CHANNEL CONTROLLER – SMALL ENCLOSURE – NO POWER SUPPLY
016ZF GM16 – 16 CHANNEL CONTROLLER – FULL WIDTH 19″ RACK – NO POWER SUPPLY
016ZH GM16 – 16 CHANNEL CONTROLLER – HALF-WIDTH 19″ RACK – NO POWER SUPPLY
064ZS GM64 – 64 CHANNEL CONTROLLER – SMALL ENCLOSURE – NO POWER SUPPLY
064ZL GM64 – 64 CHANNEL CONTROLLER – LARGE ENCLOSURE – NO POWER SUPPLY
064ZF GM64 – 64 CHANNEL CONTROLLER – FULL WIDTH 19″ RACK – NO POWER SUPPLY
128ZF GM128 – 128 CHANNEL CONTROLLER – FULL WIDTH 19″ RACK – NO POWER SUPPLY
016LS GM16 – 16 CHANNEL CONTROLLER – SMALL ENCLOSURE – LOW POWER SUPPLY (150W)
016LF GM16 – 16 CHANNEL CONTROLLER – FULL WIDTH 19″ RACK – LOW POWER SUPPLY (150W)
016LH GM16 – 16 CHANNEL CONTROLLER – HALF-WIDTH 19″ RACK – LOW POWER SUPPLY (150W)
064LS GM64 – 64 CHANNEL CONTROLLER – SMALL ENCLOSURE – LOW POWER SUPPLY (150W)
064LL GM64 – 64 CHANNEL CONTROLLER – LARGE ENCLOSURE – LOW POWER SUPPLY (150W)
064LF GM64 – 64 CHANNEL CONTROLLER – FULL WIDTH 19″ RACK – LOW POWER SUPPLY (150W)
128LF GM128 – 128 CHANNEL CONTROLLER – FULL WIDTH 19″ RACK – LOW POWER SUPPLY (150W)
016HS GM16 – 16 CHANNEL CONTROLLER – SMALL ENCLOSURE – HIGH POWER SUPPLY (600W)
016HF GM16 – 16 CHANNEL CONTROLLER – FULL WIDTH 19″ RACK – HIGH POWER SUPPLY (600W)
016HH GM16 – 16 CHANNEL CONTROLLER – HALF-WIDTH 19″ RACK – HIGH POWER SUPPLY (600W)
064HS GM64 – 64 CHANNEL CONTROLLER – SMALL ENCLOSURE – HIGH POWER SUPPLY (600W)
064HL GM64 – 64 CHANNEL CONTROLLER – LARGE ENCLOSURE – HIGH POWER SUPPLY (600W)
064HF GM64 – 64 CHANNEL CONTROLLER – FULL WIDTH 19″ RACK – HIGH POWER SUPPLY (600W)
128HF GM128 – 128 CHANNEL CONTROLLER – FULL WIDTH 19″ RACK – HIGH POWER SUPPLY (600W)
mA Input
Z 0 MA INPUTS (0 x 16 INPUT BOARDS)
A GM16 ONLY – 1 x 1-8 CHANNEL MA INPUT BOARD
B GM16 ONLY – 2 x 1-8 CHANNEL MA INPUT BOARD
C 1-16 MA INPUTS (1 x 16 INPUT BOARD)
D 1-32 MA INPUTS (2 x 16 INPUT BOARDS)
E 1-48 MA INPUTS (3 x 16 INPUT BOARDS)
F 1-64 MA INPUTS (4 x 16 INPUT BOARDS)
G 1-80 MA INPUTS (5 x 16 INPUT BOARDS)
H 1-96 MA INPUTS (6 x 16 INPUT BOARDS)
I 1-112 MA INPUTS (7 x 16 INPUT BOARDS)
J 1-128 MA INPUTS (8 x 16 INPUT BOARDS)
mV Input
Z 0 MV INPUTS (0 x 16 INPUT BOARDS)
A GM16 ONLY – 1 x 1-8 CHANNEL MV INPUT BOARD
B GM16 ONLY – 2 x 1-8 CHANNEL MV INPUT BOARD
C 1-16 MV INPUTS (1 x 16 INPUT BOARD)
D 1-32 MV INPUTS (2 x 16 INPUT BOARDS)
E 1-48 MV INPUTS (3 x 16 INPUT BOARDS)
F 1-64 MV INPUTS (4 x 16 INPUT BOARDS)
G 1-80 MV INPUTS (5 x 16 INPUT BOARDS)
H 1-96 MV INPUTS (6 x 16 INPUT BOARDS)
I 1-112 MV INPUTS (7 x 16 INPUT BOARDS)
J 1-128 MV INPUTS (8 x 16 INPUT BOARDS)
Addressable Input
Z 0 ADDRESSABLE CHANNEL INPUTS
A GM16 ONLY 1-8 ADDRESSABLE CHANNEL INPUTS
B 1-16 ADDRESSABLE CHANNEL INPUTS
C 1-32 ADDRESSABLE CHANNEL INPUTS
D 1-48 ADDRESSABLE CHANNEL INPUTS
E 1-64 ADDRESSABLE CHANNEL INPUTS
F 1-80 ADDRESSABLE CHANNEL INPUTS
G 1-96 ADDRESSABLE CHANNEL INPUTS
H 1-112 ADDRESSABLE CHANNEL INPUTS
I 1-128 ADDRESSABLE CHANNEL INPUTS
Relay output options
Z 0 RELAY OPTIONS (0 BOARDS)
A GM16 ONLY > 1 x 1-8 PROGRAMMABLE RELAY OPTIONS BOARD
B GM16 ONLY > 1 x 1-8 PROGRAMMABLE RELAY OPTIONS BOARD & 1 x 1-8 DISCREET RELAY OPTIONS BOARD (2 BOARDS)
P GM16 ONLY > 2 x 1-8 PROGRAMMABLE RELAY OPTIONS BOARD (2 BOARDS)
C 1-16 RELAY OPTIONS > 1 x 1-16 PROGRAMMABLE RELAY OPTIONS BOARD (1 BOARD)
D 1-32 RELAY OPTIONS > 2 x 1-16 PROGRAMMABLE RELAY OPTIONS BOARD (2 BOARDS)
E 1-48 RELAY OPTIONS > 2 x 1-16 PROGRAMMABLE RELAY OPTIONS BOARDS & 1 x 1-16 DISCREET RELAY OPTIONS BOARD (3 BOARDS)
F 1-64 RELAY OPTIONS > 2 x 1-16 PROGRAMMABLE RELAY OPTIONS BOARDS & 2 x 1-16 DISCREET RELAY OPTIONS BOARD (4 BOARDS)
G 1-80 RELAY OPTIONS > 2 x 1-16 PROGRAMMABLE RELAY OPTIONS BOARDS & 3 x 1-16 DISCREET RELAY OPTIONS BOARD (5 BOARDS)
H 1-96 RELAY OPTIONS > 2 x 1-16 PROGRAMMABLE RELAY OPTIONS BOARDS & 3 x 1-16 DISCREET RELAY OPTIONS BOARD (6 BOARDS)
Optional capability
0 NO OPTIONAL CAPABILITY
 GM Controllers optional Accessories & spares
GM30001 150W FIELD POWER SUPPLY -CONTACT EFS FOR OPTIONS
GM30002 600W FIELD POWER SUPPLY – CONTACT EFS FOR OPTIONS
GM40004 GM16 SMALL ENCLOSURE EXPANSION PLATE – ADDS UP TO 4 OPTION BOARDS
GM40005 GM16 FULL WIDTH 19″ RACK EXPANSION PLATE – ADDS UP TO 6 OPTIONS BOARDS
GM40003 GM64 SMALL ENCLOSURE EXPANSION PLATE – ADDS UP TO 1 OPTION BOARD
GM40002 GM64 LARGE ENCLOSURE EXPANSION PLATE – ADDS UP TO 5 OPTION BOARDS
GM40001 GM64 FULL WIDTH 19″ RACK EXPANSION PLATE – ADDS UP TO 4 OPTION BOARDS
GM40001 GM128 FULL WIDTH 19″ RACK EXPANSION PLATE – ADDS UP TO 4 OPTION BOARDS
GM20007 GM16 ANALOG OUTPUT OPTION BOARD
GM20002 GM64 / GM128 ANALOG OUTPUT OPTION BOARD
GM20010 GM16 ANALOG INPUT BOARD (1-8 INPUTS)
GM20008 GM16 PROGRAMMABLE RELAY BOARD (1-8 RELAY OUTPUTS)
GM20009 GM16 DISCRETE RELAY BOARD (1-8 RELAY OUTPUTS)
GM50011 GM16 MAIN I/O BOARD
GM50010 GM16 FRONT FASCIA DISPLAY BOARD
GM50012 GM16 BUTTON BOARD
GM50013 GM16/64/128 RS-485 ADDRESSABLE LOOP EXPANSION BOARD
GM20001 GM64 / GM128 16x MA INPUT BOARD (4-20mA)
GM20003 GM64 / GM128 DISCRETE RELAY BOARD (16 x 5A OUTPUT, SWITCHING)
GM20004 GM64 / GM128 PROGRAMMABLE RELAY BOARD (16 x 5A OUTPUT, SWITCHING)
GM50001 GM64 / GM128 – REPLACEMENT MAIN I/O BOARD
GM50002 GM64 / GM128 – REPLACEMENT COMPLETE FRONT PANEL ELECTRONIC ASSEMBLY
GM50003 GM64 / GM128 – REPLACEMENT FRONT DISPLAY SCREEN PANEL
GM50004 GM64 / GM128 / – REPLACEMENT MAIN I/O FUSE (5 x 20mm / 2 AMP)
GM50005 6 FOOT LONG 40, PIN I/O RIBBON CABLE
GM50006 16-INCH LONG 40-PIN I/O RIBBON CABLE

Enquire About This Product

Title Size
GM Addressable Controllers Datasheet 218 KB

Additional information

Weight 0.09 kg

Specifications

System configuration Ability to name the controller
Create up to eight zones which can be named
Choose how many channels are displayed simultaneously
Channel configurations Choose alarm setpoints
Select data each channel displays
Relay configurations Set value for high and lows trips for each relay
Choose colour for set trip value
Set delays to each relay option
Copy channel Copy and Paste an already configured channel to a new channel to save time for multiple identical channel configurations
Configuration upload / download Set up configuration remotely via device and download onto SD card
Inserting SD card into controller will automatically upload saved configuration
Small enclosure
– Enclosure material Fibreglass
– Dimensions 406.4 x 334.3 x 215.9mm (16.00 x 13.16 x 8.50 ins)
– Weight 7.7 Kg (17 lbs)
– Ingress Protection NEMA 4X
Large enclosure
– Enclosure material Fibreglass
– Dimensions 612.4 x 687.3 x 241.6mm (24.11 x 27.06 x 9.51 ins)
– Weight 25 Kg (55lbs)
– Ingress Protection NEMA 4X
Rack 19 inch rack mount option also available
Power Typical power use without detector heads is 20 to 50 Watts
Electrical output 4-20mA 2 wire current sink
4-20mA 3 wire current source
RS-485 Modbus RTU
Relays 5 Amp 30 Volt
RJ45 network connection
Operating temperature -20oC to + 50oC
Humidity 0 to 90% non-condensing
Repeatability and drift Digital channels – no controller variability
Analog channels – <1% FSD change over a 1 year period
Approvals May be used in a non-hazardous area as part of an intrinsically safe system
EMC compliance CE marked

Enquire About This Product