This product is obsolete and has been replaced by the FL500.
The FlameGard 5 UV/IR Flame Detector is designed to detect fires and provide alarm outputs directly from the detector while maintaining false alarm immunity. The FlameGard 5 UV/IR-H2 detects hydrogen fires.
The two models detect fires by monitoring in both the ultraviolet and infrared (UV & IR) spectral ranges, making it highly immune to false alarms caused by lightning, arc welding, hot objects and other sources of radiation.
The electronics of the FlameGard 5 UV/IR and UV/IR-H2 detectors are housed in an aluminium explosion-proof enclosure (Stainless Steel optional).
The Modbus and HART outputs provide alarm status, fault and other information for operating, troubleshooting or programming the unit. HART enables this feature without the need for rewiring. Modbus RTU (up to 128 units, or 247 units using repeaters to be linked up to a host computer)
The continuous optical path monitoring (COPM) self-test feature checks both the optical path integrity (window cleanliness) and the detector’s electronic circuitry once every minute.
Features
- A wide field of view enables greater fire detection coverage.
- Event logging stores fault and alarm history.
- 4–20 mA stepped output is the industry standard for remote alarm and fault indication.
- Modbus and HART user interface provides complete status and control capability in the control room.
- Wide operating temperature range permits operation at higher ambient temperatures.
- Continuous Optical Path Monitoring (COPM) checks the optical path integrity and the detector’s electronic circuitry once every minute.
- Three SPDT high-current programmable relay outputs provide immediate and time-delayed relay outputs for alarm, warning and fault conditions.
Applications FlameGard 5 UV/IR
- Aircraft Hangars.
- Chemical Plants.
- Compressor Stations.
- Drilling and Production Platforms.
- Electrostatic Paint Spray Booths.
- Fuel Loading Facilities.
- Gas Turbines.
- LNG/LPG Processing and Storage Facilities.
Applications FlameGard 5 UV/IR-H2
- Hydrogen Gas Generators.
- Hydrogen Refilling Stations.
- Hydrogen Storage and Test Facilities.
- Locations with Hydrogen Fuel Cells.
- Refineries.
- Rocket Fabrication, Test, and Launch Facilities.
- Semiconductor Facilities.
Order Information
5UVIR-1613132 – FlameGard 5 UV/IR, single Modbus, customer config, 4-20mA, energised relays, aluminium, ATEX, 2x M25.
5UVIR-1613232 – FlameGard 5 UV/IR, single Modbus, customer config, 4-20mA, energised relays, stainless steel, ATEX, 2x M25.
5UVIR-1613332 – FlameGard 5 UV/IR-H2, single Modbus, customer config, 4-20mA, energised relays, aluminium, ATEX, 2x M25.
5UVIR-1613432 – FlameGard 5 UV/IR-H2, single Modbus, customer config, 4-20mA, energised relays, stainless steel, ATEX, 2x M25.
5UVIR-2613132 – FlameGard 5 UV/IR, dual Modbus, customer config, 4-20mA, energised relays, aluminium, ATEX, 2x M25.
5UVIR-2613232 – FlameGard 5 UV/IR, dual Modbus, customer config, 4-20mA, energised relays, stainless steel, ATEX, 2x M25.
5UVIR-2613332 – FlameGard 5 UV/IR-H2, dual Modbus, customer config, 4-20mA, energised relays, aluminium, ATEX, 2x M25.
5UVIR-2613432 – FlameGard 5 UV/IR-H2, dual Modbus, customer config, 4-20mA, energised relays, stainless steel, ATEX, 2x M25.
5UVIR-6613132 – FlameGard 5 UV/IR, single Modbus, customer config, 4-20mA, energised relays, HART, aluminium, ATEX, 2x M25.
5UVIR-6613232 – FlameGard 5 UV/IR, single Modbus, customer config, 4-20mA, energised relays, HART, stainless steel, ATEX, 2x M25.
5UVIR-6613332 – FlameGard 5 UV/IR-H2, single Modbus, customer config., 4-20mA, energized relays, HART, 1.5mA, aluminium, ATEX, 2x M25.
5UVIR-6613432 – FlameGard 5 UV/IR-H2, single Modbus, customer config., 4-20mA, energized relays, HART, 1.5mA, stainless steel ATEX, 2x M25.
5TL-12 FlameGard 5 UV/IR Test Lamp.
10272-1 Window Cleaning Solution.
71172-2 FlameGard 5 UV/IR Bracket Assembly.