General Monitors FL3111HT High Temperature UV Flame Detector

Code: FL3111HT-1-1-1
  • Operates at high temperatures (125°C)
  • Wide field of view (110° horizontal)
  • Continuous Optical Path Monitoring (COPM)

In StockMake An Enquiry

General Monitors’ Model FL3111HT is a high-temperature-rated UV-only flame detector designed to detect unwanted fires while maintaining false alarm immunity. The FL3111HT detects only in the ultraviolet (UV) spectral range for optimised speed of response.

The detector can withstand ambient temperatures of up to 125 °C. This is achieved by using a specially selected detector and electronic components, along with very low power consumption, to minimise self-heating.

The detector’s electronics are integral within an explosion-proof housing, allowing detector information to be processed at the point of detection. The electronics are fully separated from the Exe wire compartment, offering protection during installation and service. The FL3111HT is available with a 4-20 mA stepped output.

The COPM (Continuous Optical Path Monitoring) self-test feature checks the optical path integrity (window cleanliness) and the detector’s electronic circuitry once every minute.

Features

  • Stainless steel construction
  • Exe wiring compartment
  • Fast response

Benefits

  • Suitable for gas turbine applications
  • Greater coverage for detecting fires utilising fewer detectors
  • Checks optical path integrity and the detector’s electronic circuitry once every minute
  • High level of corrosion resistance for marine environments
  • Ease of field wiring connection
  • 100 milliseconds for critical applications

Applications

  • Gas Turbines
  • Compressor Stations
  • Power Generation
  • Generator Sets
  • Solvent Extraction
  • Drying Processes
  • Paint Booths

Order Information

Part Number Description
ATEX:
FL3111HT-1-1-1 HI TEMP UV FLAME DETECTOR, 100% SENSITIVITY, 2 SECOND DELAY, ATEX/ENGLISH
FL3111HT-1-2-1 HI TEMP UV FLAME DETECTOR, 100% SENSITIVITY, 4 SECOND DELAY, ATEX/ENGLISH
FL3111HT-1-3-1 HI TEMP UV FLAME DETECTOR, 100% SENSITIVITY, 8 SECOND DELAY, ATEX/ENGLISH
FL3111HT-1-4-1 HI TEMP UV FLAME DETECTOR, 100% SENSITIVITY, 10 SECOND DELAY, ATEX/ENGLISH
FL3111HT-2-1-1 HI TEMP UV FLAME DETECTOR, 75% SENSITIVITY, 2 SECOND DELAY, ATEX/ENGLISH
FL3111HT-2-2-1 HI TEMP UV FLAME DETECTOR, 75% SENSITIVITY, 4 SECOND DELAY, ATEX/ENGLISH
FL3111HT-2-3-1 HI TEMP UV FLAME DETECTOR, 75% SENSITIVITY, 8 SECOND DELAY, ATEX/ENGLISH
FL3111HT-2-4-1 HI TEMP UV FLAME DETECTOR, 75% SENSITIVITY, 10 SECOND DELAY, ATEX/ENGLISH
FL3111HT-3-1-1 HI TEMP UV FLAME DETECTOR, 50% SENSITIVITY, 2 SECOND DELAY, ATEX/ENGLISH
FL3111HT-3-2-1 HI TEMP UV FLAME DETECTOR, 50% SENSITIVITY, 4 SECOND DELAY, ATEX/ENGLISH
FL3111HT-3-3-1 HI TEMP UV FLAME DETECTOR, 50% SENSITIVITY, 8 SECOND DELAY, ATEX/ENGLISH
FL3111HT-3-4-1 HI TEMP UV FLAME DETECTOR, 50% SENSITIVITY, 10 SECOND DELAY, ATEX/ENGLISH
RUSSIAN:
FL3111HT-1-1-2 HI TEMP UV FLAME DETECTOR, 100% SENSITIVITY, 2 SECOND DELAY, RUSSIAN W/RUSSIAN NAMEPLATE
FL3111HT-1-2-2 HI TEMP UV FLAME DETECTOR, 100% SENSITIVITY, 4 SECOND DELAY, RUSSIAN W/RUSSIAN NAMEPLATE
FL3111HT-1-3-2 HI TEMP UV FLAME DETECTOR, 100% SENSITIVITY, 8 SECOND DELAY, RUSSIAN W/RUSSIAN NAMEPLATE
FL3111HT-1-4-2 HI TEMP UV FLAME DETECTOR, 100% SENSITIVITY, 10 SECOND DELAY, RUSSIAN W/RUSSIAN NAMEPLATE
FL3111HT-2-1-2 HI TEMP UV FLAME DETECTOR, 75% SENSITIVITY, 2 SECOND DELAY, RUSSIAN W/RUSSIAN NAMEPLATE
FL3111HT-2-2-2 HI TEMP UV FLAME DETECTOR, 75% SENSITIVITY, 4 SECOND DELAY, RUSSIAN W/RUSSIAN NAMEPLATE
FL3111HT-2-3-2 HI TEMP UV FLAME DETECTOR, 75% SENSITIVITY, 8 SECOND DELAY, RUSSIAN W/RUSSIAN NAMEPLATE
FL3111HT-2-4-2 HI TEMP UV FLAME DETECTOR, 75% SENSITIVITY, 10 SECOND DELAY, RUSSIAN W/RUSSIAN NAMEPLATE
FL3111HT-3-1-2 HI TEMP UV FLAME DETECTOR, 50% SENSITIVITY, 2 SECOND DELAY, RUSSIAN W/RUSSIAN NAMEPLATE
FL3111HT-3-2-2 HI TEMP UV FLAME DETECTOR, 50% SENSITIVITY, 4 SECOND DELAY, RUSSIAN W/RUSSIAN NAMEPLATE
FL3111HT-3-3-2 HI TEMP UV FLAME DETECTOR, 50% SENSITIVITY, 8 SECOND DELAY, RUSSIAN W/RUSSIAN NAMEPLATE
FL3111HT-3-4-2 HI TEMP UV FLAME DETECTOR, 50% SENSITIVITY, 10 SECOND DELAY, RUSSIAN W/RUSSIAN NAMEPLATE

Enquire About This Product

Title Size
FL3111HT Datasheet 95 KB
FL3111HT Configurator 45 KB

Additional information

Weight 0.190 kg

Specifications

System Specifications
Wave Lengths: 185 to 260 nm
Field of View: 110° horizontal
115° vertical
Sensitivity: Approved performance specifications – 15.2 m (50 ft) distance for a 1 sq. ft. (0.092 m2)
N-heptane fire.
Typical Response Time: <1s @ 50 ft (FL3111HT)
Minimum Sensor Response Time: <100 ms
Classification: II 2 GD Ex de IIC T3, IP66
Warranty: Two years
Approvals: ATEX and CE Marking
Environmental Specifications
Operating Temperature Range: -40°C to +125°C
(-40°F to +257°F)
Storage Temperature Range: -40°C to +125°C
(-40°F to +257°F)
Operating Humidity Range: 0% to 100% RH, non-condensing
Pressure Range: 80 kPa (0.8 bar) to 110 kPa (1.1 bar)
Mechanical Specifications
Housing: Stainless steel
Diameter: 84 mm (3.3 in)
Length: 136 mm (5.3 in)
Weight: 2.27 kg (5 lbs)
Cable Entries: 2 x M20
Electrical Specifications
Input Power: 20-36 VDC
24 VDC @ 60 mA typ / 85 mA max.
Analogue Signal: 4-20 mA (350 Ohms max.)
Fault Signal: 0 mA
COPM Fault: 2.0 ± 0.4 mA
Ready Signal: 4.0 ± 0.4 mA
WARN Signal: 16.0 ± 0.4 mA
ALARM Signal: 20.0 ± 0.4 mA
Selectable Options: Sensitivity: 100%, 75%, 50%
Alarm Time Delay: 2, 4, 8 or 10 seconds
RFI/EMI Protection: Complies with EN50270, Type 2
Exe Terminal: 0.75 – 2.5 mm2 (12-22 AWG)
Cable Requirements: 3 wire shielded cable minimum configuration. Maximum distance between FL3111HT and power source or remote sensor @ 24 VDC nominal (20 Ohms loop):
14 AWG – 2,250 m (7,400 ft)
Maximum distance for analog output
(250 Ohms termination max):
14 AWG – 2,750 m (9,000 ft)
Status Indicators: Two LED’s with status and fault cues
Fault Monitoring: Optics failure/blockage and low supply voltage

Enquire About This Product