Micronics UF DS200 Flow Switch

Code: 1000-1017
  • No moving parts
  • Installs in minutes
  • No contact, no maintenance

In StockMake An Enquiry

Flow Switch with Non-Contacting Sensor

Mount the UF DS200 ultrasonic sensor on the outside of metal or plastic pipes. The sensor continuously injects high-frequency sound through the pipe wall and into the moving fluid, where acoustic pulses are reflected back to the sensor from particles or bubbles in the fluid.

Flow rates of most liquids can be accurately controlled, including acids, caustics, lubrication fluids, chemicals, abrasives, waste water and sludge. There are no moving parts, and no sensor maintenance is required.

The compact, water-tight electronics enclosure includes adjustable controls with separate ON and OFF relay set-points and time delay. An LED bargraph for flow rate, set points, and relay status is included.

Installation can be made while the flow system is in full operation. No contact is made with the moving fluid, and no holes are drilled in the pipe. There is no fouling or scale build-up on the sensor.

Easy to Calibrate

The UF DS200 control relay can be set to turn ON and OFF at any flow rate between 0.075 to 3 m/sec (0.25 and 10 ft/sec). Insert two links for separate ON/OFF set points or just one link for a Hi or Lo flow alarm. Set the relay actuation time delay from 0 to 80 seconds.

Ideal for Pump Protection

Avoid expensive pump repairs and downtime. The UF DS200 strap-on Sensor can be installed in minutes without shutting down the flow or cutting the pipe. Use the adjustable relay time delay to eliminate relay “chatter” and reduce pump wear.

Reliable and Repeatable

Repeatability is ±0.1% of full scale (0.003 m/sec or 0.1ft/sec). There are no moving parts, and no maintenance is required. The clamp-on ultrasonic sensor cannot be damaged or fouled by contact with the liquid it measures.

Sealed in a stainless steel housing, the UF DS200 sensor withstands moisture or accidental submersion in water up to 10 psi (69 kPa).

Self-tunes to Extended Sensor Cable

An extra sensor coaxial cable of up to 150 m (500 ft) can be added. An extended cable and junction box can be ordered. The cable can be cut or extended as required during installation. The flow switch automatically tunes to the cable length. No circuit adjustment or calibration is required.

Designed for “difficult” liquids

The UF DS200 Doppler Flow Switch is recommended for flow control of liquids containing gas bubbles or solids: chemicals, slurries, sewage, sludge, viscous liquids, wastewater, caustics and abrasives.

The ultrasonic sensor injects high-frequency sound through the pipe wall into the flowing liquid. Acoustic pulses are continuously reflected back to the sensor, and the UF DS200 measures a frequency shift to calculate flow velocity.

Enquire About This Product

Title Size
DS200 Datasheet 273 KB
DS200 User's Guide 841 KB

Additional information

Weight 0.09 kg

Specifications

General Specifications
Shipping Weight: 3.6kg (8 lbs)
Enclosure: Watertight, dust tight NEMA4X (IP67) polycarbonate with a clear shatter-proof face
Power Input: 100-240VAC 50-60Hz (±10%), 2 Watts
Control Relay: 5 ampere DPDT
Set Points: ON/OFF adjustment from 0.075 to 3 m/sec (0.25 to 10 ft/sec)
Sensor: Single-head ultrasonic with 6 m (20 ft) shielded cable
Pipe Size: Any pipe ID from 12.5 mm to 4.5 m (½” to 180”)
Sensor Operating Temperature: -40° to 150°C (-40° to 300°F)
Electronics Operating Temperature: -23° to 60°C (-10° to 140°F)
Accuracy: ±2%, requires solids or bubbles minimum size of 100 microns, minimum concentration 75 ppm.
Repeatability: ±0.1%
Standard Features
Set-point: Field-adjustable with separate ON/OFF set-points or select Hi flow alarm or Lo flow alarm mode
Indication: Fow rate LED bargraph, relay status LED
Time Delay: Adjustable 0 to 80 seconds
Electrical Surge Protection: AC power input and sensor
Sensor mounting bracket, clamp and coupling compound included
Options
Sensor Cable: Up to 150 m (500 ft) shielded coaxial pair with cable Junction Box
Sensor mounting clamp: Stainless steel, adjustable
Power input: 12-24 VDC (±10%), 3W Max
Applications Recommended for liquids containing suspended solids or bubbles minimum size of 100 microns, minimum concentration 75 ppm
Sensor mounts on Vertical or Horizontal pipes
Sensor Mounting Location: 6-10 pipe diameters from elbows, tees (turbulence increasing devices)
>30 pipe diameters from pumps, controlling valves and pipe discharge
Pipe Materials: steel, stainless steel, cast iron, PVC, fiberglass, any contiguous pipe material that conducts sound, including lined pipes with liner bonded to pipe wall. Avoid pipes with loose insertion liners and pipe materials which contain air pockets (concrete, wood etc.)

Enquire About This Product