ABB Furse ESP 240-16A Surge Protector

Code: 7TCA085460R0080
  • Nominal voltage 240 V
  • Repeated protection in lightning-intense environments
  • Maintenance free

In StockMake An Enquiry

The ESP240-16A is a combined type 2 and 3 tested protector (to BS EN 61643) for use on low current (up to 5 or 16 A) single-phase systems to protect connected electronic equipment from transient overvoltages on the mains supply, e.g., fire/intruder alarm panels. Protectors with /BX suffix come ready-boxed to IP66.

For use at boundaries LPZ 1 through to LPZ 3 to protect sensitive electronic equipment.

Features & Benefits

  • Very low let-through voltage (enhanced protection to IEC/BS EN 62305) between all sets of conductors (phase to neutral, phase to earth, neutral to earth – Full Mode protection), allowing continuous operation of equipment.
  • Compact size for easy incorporation in the protected system.
  • Removable DIN rail foot for simple clip-on mounting to top hat DIN rails (unboxed versions).
  • Colour-coded terminals give a quick and easy installation check – grey for the dirty (line) end and green for the clean end.
  • Available ready-boxed to IP66 for use in dirty or damp environments (protectors with /BX suffix).
  • Robust housing and substantial earth stud fixing holes ready for flat mounting.

Application

Use these protectors on low-current mains power supplies, e.g. CCTV cameras, alarm panels and telemetry equipment.

Installation

Connect in line with the power supply, usually either within the equipment panel (or, for CCTV cameras, in an enclosure close by) or on the fused connection that supplies equipment.

To protect equipment inside a building from transients entering on an outgoing feed (e.g. to CCTV cameras or to site lighting), the protector should be installed as close to where the cable leaves the building as possible.

Unless ready-boxed, protectors should be installed either within an existing cabinet or cubicle or in a separate enclosure.

Specifications

  • Nominal voltage – Phase-Neutral Uo (RMS) 240 V
  • Maximum voltage – Phase-Neutral Uc (RMS) 280 V
  • Working voltage (RMS) 200-280 V
  • Frequency range 47-63 Hz
  • Current rating (supply) 16 A or less
  • Max. backup fuse (see installation instructions) ≤ 16 A
  • Leakage current (to earth) < 0.5 mA
  • Temperature range -40 to +80 °C
  • Connection type Screw terminal – maximum torque 0.5 Nm
  • Conductor size (stranded) 4 mm2
  • Earth connection Via M6 stud or earth terminal -maximum torque 0.5 Nm
  • Cable glands 5A/BX 4.8-8 mm cable (PG9)
  • Degree of protection (IEC 60529) IP66
  • Case Material PVC
  • Weight: – Unit 0.26 kg. Packaged 0.31 kg
  • CN8: 8536308000

Enquire About This Product

Title Size
ESP 240-16A/BX Datasheet 644 KB

Additional information

Weight 0.09 kg